Chapter 7 Use the 1769-SDN Scanner Module with MicroLogix Controllers

The configuration dialog for the scanner module is shown below.

Ignore Configuration Error

Checking (enabling) the Ignore Configuration error checkbox instructs the
module to ignore I/O size mismatches. If this is checked and the input/output
scanlist configured by RSNetWorx for DeviceNet software (DeviceNet side of
the 1769-SDN scanner module) does not match the amount of I/O data
assigned by the controller (0...180 words), the module will not generate an
error.

If this checkbox is not checked, the number of data words on the controller
side must match the number of words configured by RSNetWorx for
DeviceNet software. The default condition is unchecked (report an error on
mismatch).

Series/Major Rev/Minor Rev

You will need this information if you contact Rockwell Automation Technical
Support.