What you need to do – Rockwell Automation 1769-SDN Compact I/O DeviceNet Scanner Module User Manual User Manual
Page 20
20
Publication 1769-UM009E-EN-P - August 2009
Chapter 2 Quick Start for Experienced Users
What You Need to Do
Follow these steps to get started using the 1769-SDN scanner module.
1.
Verify planned system configuration.
a. Ensure system power supply has sufficient current.
The scanner module cannot be located more than four modules away
from the system power supply.
b. Verify that the DeviceNet network has adequate power.
2.
Remove power.
Maximum Current Draw
Module
5V DC
24V DC
1769-SDN
440 mA
0 mA
DeviceNet Power Requirements
Module
DeviceNet Power Requirements
1769-SDN
N.E.C. Class 2
90 mA @ 11V DC, max.
110 mA @ 25V DC, max.
200 mA for 1.5 ms inrush
ATTENTION
Remove power before removing or inserting this module. When
you remove or insert a module with power applied, an electrical
arc may occur. An electrical arc can cause personal injury or
property damage by:
• sending an erroneous signal to your system’s field devices,
causing unintended machine motion.
• causing an explosion in a hazardous environment.
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector and can lead to premature
failure.