Chapter 3 Installation and Wiring

Field Wiring Connections

Follow these procedures to wire the scanner module.

Grounding the Scanner Module

This product is intended to be mounted to a well-grounded mounting surface,
such as a metal panel. Additional grounding connections from the scanner’s
mounting tabs or DIN rail (if used), are not required unless the mounting
surface cannot be grounded.

For additional information on grounding the scanner module, refer to
Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley
publication

1770-4.1

.

DeviceNet Wiring

ATTENTION

The grounding screw on the front of the scanner module must
be connected to a suitable ground source when operating in

electrically noisy environments. Use a 2.1 mm

2

(14 AWG) wire

to make this connection.

DeviceNet
Connector

Connect

(1)

(1)

DeviceNet cable colors are shown on the
wiring label on the front of the scanner

To

Red Wire

V+

White Wire

CAN High

Bare Wire

Shield

Blue Wire

CAN Low

Black Wire

V-

Grounding Screw

Use 2.1 mm

2

(14 AWG

wire to connect to
panel ground.