Active node array scanner module status, Active node array, Scanner module status – Rockwell Automation 1769-SDN Compact I/O DeviceNet Scanner Module User Manual User Manual

Page 91

Advertising
background image

Publication 1769-UM009E-EN-P - August 2009

91

DeviceNet I/O Image Chapter 6

Active Node Array

The Active Node array contains 64 bits of data that represents each slave
node’s status. A slave node is considered active when it is present and enabled
in the master’s scanlist. A bit value of 0 means Not Active, a bit value of 1
means Active.

Scanner Module Status

The Scanner Device Status is a 4-byte array.

Slave Node Status

Input Word

Bit 0...15

Description

14

(1)

(1)

Bit 0 corresponds to Node 0, Bit 1 corresponds to Node 1 … Bit 15 corresponds to Node 15.

Node 0…15

Bit ON (1) = Active node

Bit OFF (0) = Inactive node

15

(2)

(2)

Bit 0 corresponds to Node 16, Bit 1 corresponds to Node 17 … Bit 15 corresponds to Node 31.

Node 16…31

16

(3)

(3)

Bit 0 corresponds to Node 32, Bit 1 corresponds to Node 33 … Bit 15 corresponds to Node 47.

Node 32…47

17

(4)

(4)

Bit 0 corresponds to Node 48, Bit 1 corresponds to Node 49 … Bit 15 corresponds to Node 63.

Node 48…63

Scanner Device Status

Input Word

Bit

Description

20

0…7 (lower byte)

Scanner Address in BCD

8…15 (upper byte)

Scanner Status in BCD

21

0…7 (lower byte)

Slave Device Address in BCD

8…15 (upper byte)

Slave Device Status in BCD