Set the node address of a device via a devicenet, Configuration terminal – Rockwell Automation 1769-SDN Compact I/O DeviceNet Scanner Module User Manual User Manual

Page 42

Advertising
background image

42

Publication 1769-UM009E-EN-P - August 2009

Chapter 4 Automatically Configure a DeviceNet Network

Set the Node Address of a Device Via a DeviceNet
Configuration Terminal

Follow these steps to set the node address of a device on your DeviceNet
network via the 193-DNCT terminal.

1.

Connect the 193-DNCT terminal to the network. The following display
should appear for 10 seconds that shows the unit setup and the baud
rate and node number values it has determined.

After 10 seconds a Network Who screen similar to the example shown
below should appear that displays all Nodes and associated devices on
the network.

2.

Use <Down Arrow>

on the 193-DNCT terminal to scroll down

through the list until the last entry for node 63 is highlighted, which
should read 63 - No Product Name.

3.

Press <Enter>

to advance to the configuration screen.

4.

Use <Down Arrow>

to select the Tools option.

Actual Terminal
Node Address

Address = Fixed HMI MacID
Auto = Auto Addressing

Actual Baud Rate

baud = Fixed Baud Rate
Auto = Autobaud

Advertising