Chapter 8 Troubleshooting

This table summarizes the meanings of the status indicators and numeric
codes.

Module Indicator

Network Indicator

Node Address and
Status Display

Troubleshooting the Status Indicators and Numeric Display

Indicator

Color/Status

Description

Module

Off

No power applied to module.

Apply power.

Flashing
Green

No bus master (MicroLogix or CompactLogix controller) present.

Verify module connectors are properly seated. If they are, cycle power to the controller. If this does not
correct the problem, replace the controller. If replacing the controller does not correct the problem,
replace the scanner.

Solid Green

Normal operation.

Flashing Red

• Recoverable Fault - Memory has been erased or is being programmed. Complete the flash update or

start a new update.

• Bad firmware in module. Replace firmware.

Solid Red

Unrecoverable fault.

Verify module connectors are properly seated. If they are, verify that bus terminator/end cap is installed.
Cycle power. If still faulted, replace the module.