Initiate autoscan via the 193-dnct terminal – Rockwell Automation 1769-SDN Compact I/O DeviceNet Scanner Module User Manual User Manual

Page 51

Advertising
background image

Publication 1769-UM009E-EN-P - August 2009

51

Automatically Configure a DeviceNet Network Chapter 4

Initiate AutoScan via the 193-DNCT Terminal

Follow these steps to enable AutoScan using the 193-DNCT terminal, version
2.1 or higher.

1.

Put your controller into Program mode, and verify that the scanner is in
Idle mode (CommandRegister.Run = 0) and that all slave nodes are
connected and communicating on the DeviceNet network.

2.

Plug the 193-DNCT terminal into the DeviceNet network.

3.

In the Network Who dialog, press <Up Arrow>

to navigate to and

select the first line (0 - 1769-SDN DeviceNet Scanner).

4.

Press <Enter>

to go to the scanner’s configuration dialog.

5.

Press <Down Arrow>

to navigate to Scanner and press <Enter>

.

6.

Press <Down Arrow>

to navigate to AutoScan and press

<Enter> .

The AutoScan Setup dialog appears.

7.

If AutoScan is selected and set to Enable, press <Up Arrow>

to

change the setting to Disable.

8.

Press <SEL>

to scroll down to Save. This disable the AutoScan

feature.

9.

Press <SEL>

to scroll down to Mapping.

10.

Type in the number of bytes that you want to automap to each
DeviceNet node, that is, 1…32. The default is 4 bytes.

11.

Press <SEL>

to scroll down to Save, and press <Enter>

to

commit your byte size selections.

The AutoScan feature is now configured with the byte size entered in

step 9