Automatically Configure a DeviceNet Network Chapter 4

2.

Set up I/O allocation size in the scanner.

The default AutoScan setting allocates a 4-byte entry in both the input
and output memory maps in the scanner for each slave device detected
on the network. This default size is chosen to accommodate the default
Logix native data size of 32 bits (DINT). If that is adequate for the
application, skip to

step 3

.

For applications where the user would like to customize the I/O
allocation size, the 4-byte allocation could be adjusted through an
Explicit Message to the scanner using the SetAttributeSingle service.
The entry allocation could be configured for 1 to 32 bytes per node.
One way to set the allocation size is described in section

Configure I/O

Allocation Size Via the User Program.

The following table lists devices that most commonly use the
AutoScan feature and their respective I/O allocation sizes.

TIP

This step is optional.

Device

Bulletin Number

Input Allocation

Output
Allocation

ArmorStart Distributed
Motor Controller

280D/281D

1 byte

1 byte

193-E Electronic
Overload Relays

193

8 bytes

1 byte

PowerFlex 40
Adjustable Frequency
AC Drive

22B

4 bytes

4 bytes