Chapter 1 Overview

Input Data Image - CompactLogix

The input data image is transferred from the scanner module to the controller
across the Compact I/O bus.

Output Data Image - CompactLogix

The output data image is transferred from the controller to the scanner
module across the Compact I/O bus.

For additional information about the CompactLogix image structure, refer to
the DeviceNet Modules in Logix5000 Control Systems User Manual,
publication

DNET-UM004

.

Module Command Array Bit Assignments

Output
Word

Bit

Description

Behavior

0

0

Run

This bit controls when the module scans its
mapped slave devices. When set (1), the
scanner module will process I/O data as
defined by its scanlist. The Fault and Disable
Network command bits must be clear (0) to
scan the network.

1

Fault

When set, the scanner’s I/O mode will be
Halt; messaging will still operate. The fault
bit is primarily used to artificially set the
slave devices into a fault state due to some
event or condition within the control
program.

2

Disable network

When set, the scanner module is
functionally removed from the network.

3

Reserved

(1)

N/A

4

Reset

Restarts access to the DeviceNet network.

5…15

Reserved

(1)

N/A

1

16…31

Reserved

(1)

N/A

(1)

Do not manipulate reserved bits. Doing so may interfere with future compatibility.

Word

Description

Data Type

0…89

DeviceNet slave inputs

90-DINT array

Word

Description

Data Type

0…89

DeviceNet slave outputs

90-DINT array