Publication 1734-UM003B-EN-P - August 2005

About the Modules 1-5

X4 Multiplying Encoder Mode

Quadrature input signals are used to count on leading and trailing
edges of A and B for a bidirectional count, and channel B is used to
determine the direction.

[ B = leads A, Count = Down; B = follows A, Count = Up ]

Period/Rate Mode

The Period/Rate mode returns an incoming frequency and a total
accumulated count to the POINTBus, by gating an internal 5 MHz
internal clock with an external signal.

This mode determines the frequency and total number of input pulses
by counting the number of internal 5MHz clock pulses over a
user-specified number of input signal pulses. At the end of the
specified number of pulses, the module returns the frequency
(0 - 1 MHz). When the frequency is updated, both outputs are
checked against their associated presets.

EXAMPLE

Example of Period/Rate Mode

A ( Not Used )

B ( Not Used )

Encoder / Pulse Generator

1734-VHSC

Input A

Input B

Z Input ( Pulse )

5 MHz Internal

(Gate / Reset )

Input Z

Z

Accumulated Count

1

Scalar

5 MHz Clk

Sampling Clock

Assumes symmetrical pulse, 50% duty cycle, so Period = Sample Time On X 2 {On & Off}

10

20

Frequency = 1 / Period If Count = 20, Scalar = 1, and Clock Period = ( 1 / 5 MHz )
Frequency = 1 / [ ( 20 / 1 ) X ( 1 / 5 MHz ) X 2 ] = 125 kHz

Frequency & Outputs
Updated Here