Very High-Speed Counter Module Input and Output Data 3-9

Scalar (Configuration Word 7)

This byte scales the Z signal in the period/rate [5] and continuous/rate
[6] configurations. If the filter is applied, then the filtered Z is scaled.
Only one bit of the scalar should be set. Selecting a scalar causes
accumulated counts to be adjusted accordingly. Selecting a scalar of
128 increases the accumulated count by 128 after 128 Z pulses are
received. We highly recommend that anytime Z is scaled (divide by 2,
4, 8...), the Z input should be filtered; otherwise, noise could cause
erroneous frequency readings.

Scalar Selection

Output 0-1 Ties (Configuration Words 8 and 9)

The bits in these two bytes connect the specified output to the
appropriate compare window. There are 4 windows associated with
the counter. Each output may be connected to any number of
windows, from 1 to all 4. The bits are defined as follows:

T0 -

Tie Output to 1st Compare Window (also the PWM signal in
PWM [3] configuration)

T1 -

Tie Output to 2

nd

Compare Window

T2 -

Tie Output to 3

rd

Compare Window

T3 -

Tie Output to 4

th

Compare Window

07

06

05

04

03

02

01

00

Scalar

1

0

0

0

0

0

0

0

1

Z - F

min

= 0.149 Hz

0

0

0

0

0

0

1

0

Z/2 - F

min

= 0.298 Hz

0

0

0

0

0

1

0

0

Z/4 - F

min

= 0.596 Hz

0

0

0

0

1

0

0

0

Z/8 - F

min

= 1.192 Hz

0

0

0

1

0

0

0

0

Z/16 - F

min

= 2.384 Hz

0

0

1

0

0

0

0

0

Z/32 - F

min

= 4.768 Hz

0

1

0

0

0

0

0

0

Z/64 - F

min

= 9.537 Hz

1

0

0

0

0

0

0

0

Z/128 - F

min

= 19.073 Hz

1 Where F

min

indicates the frequency at which the zero frequency detect is asserted

due to counter overflow.