Publication 1734-UM003B-EN-P - August 2005

About the Modules 1-11

Store Count Mode 2: Store/Wait/Resume

In mode 2, the rising edge of a pulse input on the Z Gate/Reset
terminal reads and stores the current counter value in the
Stored/Accumulated Count word and inhibit counting while the Z
Gate/Reset terminal is high. Counting resumes on the falling edge of
the pulse at the Z Gate/Reset terminal. The stored count information
remains until it is overwritten with new data.

Store/Wait/Resume

Store Count Mode 3: Store-Reset/Wait/Start

In mode 3, the rising edge of a pulse input on the Z Gate/Reset
terminal stops counting, reads, and stores the current counter value in
the Stored/Accumulated Count word, and resets the counter to zero.
The counter does not count while the input pulse on the Z Gate/Reset
terminal is high. Counting resumes from zero on the falling edge of
the pulse at the Gate/Reset terminal. The stored count information
remains until it is overwritten with new data.

Store-Reset/Wait/Start

Store Count Mode 4: Store-Reset/Start

In mode 4, the rising edge of a pulse input on the Z Gate/Reset
terminal stores the current counter value in the Stored/Accumulated
Count word and reset the counter to zero. The counter continues
counting while the Z Gate/Reset terminal is high. The stored count
information remains until it is overwritten with new data.

Store Count

Resume Counting

Stop Counting

and Reset to zero

from zero

Counter has stopped Counting

Start Counting

Stop Count, Store,