1-10 About the Modules

Operating Mode Features

See the table for a summary of features active in each mode.

Operating Mode Features

The Z Gate/Reset Terminal operates in one of four modes when the
Store Count feature is in use. The four figures below detail the
operation in each mode.

Store Count Mode 1: Store/Continue

In mode 1, the rising edge of a pulse input on the Z Gate/Reset
terminal causes the current counter value to be read and stored in the
Read Data file. The counter continues counting. The stored count is
available in the Stored/Accumulated Count word. The stored count
information remains until it is overwritten with new data.

Store/Continue

Operating Feature

Counter
Up / Down

Encoder
X1, X2 & X4

Period
/Rate

Continuous
/Rate

Rate
Measurement

PWM

Preset

Y

Y

N

N

N

N

Rollover

Y

Y

N

N

N

N

Software Reset

Y

Y

Y

Y

Y

Y

Store Count -
Z Gate / Reset
4 modes

Y

Y

N

N

N

N

Scale Input Count at
Z Gate / Reset

N

N

Y

Y

N

N

Z Gate / Reset Invert Bit

Y

Y

Y

Y

N

N

Enable /Force Outputs

Y

Y

Y

Y

Y

Y

Assign Outputs

Y

Y

Y

Y

Y

Y

Operate Outputs
(Based On)

Y
(Count)

Y
(Count)

Y
(Count)

Y
(Count)

Y
(Count)

Y
(PWM Value)

Sample Period

N

N

N

N

Y

Y

Read, Store Count,
and Continue Counting

Advertising