Very High-Speed Counter Module Input and Output Data 3-11

Safe State Values (Configuration Words 20 through 22)

When either the host transitions to PROGRAM mode or a
communication fault (broken network cable) occurs, the module
copies these safe state words (counter control, output control, and
PWM value) into its real-time working buffer. The definitions are
identical to those described under Real-time Output Data with the
following exception: entering a PWM Safe State value outside of the
range, 0-9500, results in a Hold Last State to be executed.

Communicating Real Time
Information

The Very High-Speed Counter Module uses several words to
communicate real time input and output data as well as non-real time
module information (such as description and revision) and
configuration.

Assembly 101 is produced for a polled connection. Assembly 102 is
produced for a Change Of State (COS) connection. Assemblies 103,
104, 107 and 108 are by Explicit message only. Assemblies 105 and
106 are consumed in a polled connection (as directed by parameter
4).

Data may be read (get) or written (set) using an Explicit Message. For
example, to read the Present Channel Data, assembly 101

10

(65

16

) can

be requested. The following table shows the words which can be
exchanged.

Instances

Services

Field

Bytes

#101 (0x65)

Get

Present Channel Data

4

Status

2

#102 (0x66)

Get

Stored Channel Data

4

Status

2

#103 (0x67)

Get

Present Channel Data

4

Stored Channel Data

4

Status

2

#104 (0x68)

Get

Programming Error Code

2

#105 (0x69)

Set/Get

Counter Control

1

Output Control

1

#106 (0x6a)

Set/Get

PWM Value

2

#107 (0x6b)

Set/Get

PWM Value

2

Counter Control

1

Output Control

1