Operation of scalar – Rockwell Automation 1734-VHSC24 Very High-Speed Counter Modules User Manual User Manual

Page 16

Advertising
background image

Publication 1734-UM003B-EN-P - August 2005

1-6 About the Modules

As the frequency of the incoming pulse train at the Z (Gate/Reset)
terminal increases, the number of sampled pulses from the 5MHz
clock decreases. Since accuracy is related to the number of pulses
received over the sample period, the accuracy decreases with
increasing frequencies at the Gate/Reset terminal. Refer to the
following Scaling table.

Scaling the input frequency through the use of a scalar can lessen the
decrease in accuracy. A scalar value of 1 returns an accurate input
frequency if incoming input pulses have a 50% duty cycle.

Operation of Scalar

In the Period/Rate mode, the scalar lets the incoming pulse train at the
Z Gate/Reset pin be divided by a user-defined number. There is one
scalar value for each counter. Acceptable values for the scalar are 1,
2, 4, 8, 16, 32, 64, and 128. The default value for each scalar is 1.
Note that a 0 scalar is equivalent to a 1.

The product of the Sample Period times the scalar should be less than
6.71 seconds in order to avoid a zero frequency detect indication.

(5 MHz sample time = 200ns; 16,777,216 counts x 200ns x 2 half cycles
of Z = 6.71 seconds)

Relationship Between Sampled Pulses and Input Frequency

Input Frequency at Z Gate/Reset Terminal

Sample Pulses for 1/2 Cycle of Z Gate/Reset Pulse

2.5 Hz

1 M

5 Hz

500 k

10 Hz

250 k

20 Hz

125 k

50 Hz

50 k

100 Hz

25 k

200 Hz

12.5

500 Hz

5 k

1k Hz

2.5 k

2 Hz

1.25 k

5 kHz

500

10 kHz

250

20 kHz

125

50 kHz

50

100 kHz

25