What this chapter contains, Data table, Chapter – Rockwell Automation 1734-VHSC24 Very High-Speed Counter Modules User Manual User Manual

Page 31

Advertising
background image

1

Publication 1734-UM003B-EN-P - August 2000

Chapter

3

Very High-Speed Counter Module Input and
Output Data

What This Chapter Contains

In this chapter, you learn about the input and output data table of
your 1734-VHSC24 and 1734-VHSC5 Modules.

Data Table

The following table shows the complete format of the input and
output data.

For More Information About

See Page

Data Table

3-1

Detailed Description of Data Table Information

3-2

Output Data

3-5

Configuration Data

3-6

Communicating Real Time Information

3-11

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

0

Input Information

Present Channel Data

32-bit Value of the present counter state

Stored Channel Data

32-bit value of the stored/accumulated count

Status

PE

EF

NR

0

FS

FS

OS

OS

0

ZS

BS

AS

C1

C0

ZD

0

Programming Error Code

PE

0

0

0

0

E10

E9

E8

E7

E6

E5

E4

E3

E2

E1

E0

Output Information

Counter Control

0

0

0

0

0

VR

CP

CR

Output Control

DS

ES

OE

FO

DS

ES

OE

FO

PWM Value

16-bit decimal value with range from 0-9500 (0-95.00%)

Configuration Information

Counter Configuration

ZI

MD

MD

MD

CF

CF

CF

CF

Filter Selection

0

ZF

BF

AF

FS

FS

FS

FS

Decimal Position

8-bit value used to modify the present channel data display

Active Output Assembly

Assembly number (0, 105 or 106)

Time Base/PWM Period

16-bit value used to set the time base or PWM period

Gate Interval

8-bit value used to set the gate interval

Advertising
This manual is related to the following products: