Publication 1734-UM003B-EN-P - August 2005

Configure Modules in RSLogix 5000 Software A-3

Configure Your Module

To configure your module in RSLogix 5000, use this procedure.

1. Configure your adapter, referring to the user manual for your

adapter for information on how to configure the adapter and
add modules to the I/O configuration to include selecting a
controller and communication module.

2. Add a 1734-VHSC3 or 1734-VHSC24 specialty module, according

to the instructions in your adapter user manual.

3. From the Connection dialog, select a value for the Requested

Packet Interval (RPI) entry.

• Default value is 80.0 milliseconds.
• Range is 2.0 to 750.0 milliseconds.

4. From the Connection dialog, leave these unchecked.

• Inhibit Module
• Major Fault On Controller If Connection Fails While in Run

Mode

5. Complete entries for these dialogs, as explained in this chapter.

• Fault/Program Action
• Counter Configuration
• Output Configuration

Use the Help Button

From the Fault/Program Action, Counter Configuration, and Output
Configuration dialogs, click Help at the bottom of the dialog for
information about how to complete entries on the dialogs.

From a warning dialog, click Help at the bottom of the dialog to get
information about that specific error.