Publication 1747-UM010B-EN-P - September 2003

9-6 Programming Techniques

0012

B3:3

11

COP

Copy File
Source #M1:1.4908
Dest

#N17:128

Length

128

COP

B3:4

11

0013

B3:3

12

COP

Copy File
Source #M1:1.5036
Dest

#N18:0

Length

128

COP

B3:4

12

0014

B3:3

13

COP

Copy File
Source #M1:1.5164
Dest

#N18:128

Length

128

COP

B3:4

13

0015

B3:3

14

COP

Copy File
Source #M1:1.5292
Dest

#N19:0

Length

128

COP

B3:4

14

This rung copies the "new" Data Block #12 data from the secondary 1747-BSN to a file within the secondary processor. When the Copy is
complete, the DTHW (Data Table Handshake Word) bit for Data Block #12 (B3:4/11 = M0:1.3411/11) must be set to inform the secondary
1747-BSN that the secondary processor has received the latest Data Block and is now ready for the next block of data via Data Block #12.

This rung copies the "new" Data Block #13 data from the secondary 1747-BSN to a file within the secondary processor. When the Copy is
complete, the DTHW (Data Table Handshake Word) bit for Data Block #13 (B3:4/12 = M0:1.3411/12) must be set to inform the secondary
1747-BSN that the secondary processor has received the latest Data Block and is now ready for the next block of data via Data Block #13.

This rung copies the "new" Data Block #14 data from the secondary 1747-BSN to a file within the secondary processor. When the Copy is
complete, the DTHW (Data Table Handshake Word) bit for Data Block #14 (B3:4/13 = M0:1.3411/13) must be set to inform the secondary
1747-BSN that the secondary processor has received the latest Data Block and is now ready for the next block of data via Data Block #14.

This rung copies the "new" Data Block #15 data from the secondary 1747-BSN to a file within the secondary processor. When the Copy is
complete, the DTHW (Data Table Handshake Word) bit for Data Block #15 (B3:4/14 = M0:1.3411/14) must be set to inform the secondary
1747-BSN that the secondary processor has received the latest Data Block and is now ready for the next block of data via Data Block #15.

Virtual DTHW bit for Data Block #12

Virtual DTHW bit for Data Block #13

Virtual DTHW bit for Data Block #14

Virtual DTHW bit for Data Block #15

Virtual DTSW bit for Data Block #12

Virtual DTSW bit for Data Block #13

Virtual DTSW bit for Data Block #14

Virtual DTSW bit for Data Block #15