Overview 1-15

Summary for Placing Modules Used In Complementary I/O

Discrete Modules

Block Transfer Modules

The following example illustrates how I/O modules requiring two
words of the input or output image can leave unused image space.

Addressing
Method

Types of Modules
used

Placement

2-slot

8-point

Install input modules opposite output modules,
and output modules opposite input modules.

(1)

(1) If an input module resides in either slot, associated with a logical group, of the primary chassis, an input

module cannot reside in that logical group’s complimentary chassis.

1-slot

8-point, 16-point

Install input modules opposite output modules,
and output modules opposite input modules.

1/2-slot

8-point, 16-point,
32-point

Install input modules opposite output modules,
and output modules opposite input modules.

Addressing
Method

Placement

2-slot

The right slot of the primary I/O group can be another block transfer
module, or an 8-point input or output module.

The left slot of the complementary I/O group must be empty.

In the right slot of the complementary I/O group, you can place an
8-point output module; this slot must be empty if the corresponding