Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 56

Advertising
background image

Publication 1747-UM010B-EN-P - September 2003

4-4 Operating Your SLC 500 Backup System

Secondary Processor Remote Programming

In the 1747 backup system, only the primary processor is connected
to the link. The secondary processor is not physically connected, but
it communicates with the secondary 1747-BSN module making this
processor think that it is on the DH+ network. This separate link
prevents Data Highway faults in the secondary processor.

Primary

Secondary

SLC 5/04

1747-BSN

Remote I/0 Link

1747-BSN

SLC 5/04

Primary

Secondary

SLC 5/04

1747-BSN

DH+ Network

1747-BSN

SLC 5/04

HSSL

1747-SN

emulation

1747-SN

emulation

RIO

HSSL

DH+

IMPORTANT

The programming device must be connected through
the DH+ network and must not bypass the relay in
the 1747-BSN module (if the programs in both
processor are identical; e.g., if both DH+ mode
addresses are the same). If you were to connect the
device directly to a processor, it must be connected
to the primary processor. Therefore, if your system
were to switch to the secondary system, you must
then move your device to your new primary
processor.