Installation and Wiring 3-9

RS-232/RS-485 Network Wiring

The 1747-BSN module supports RS-232 or RS-485 communications for
the primary processor only. The RS-232 or RS-485 network can use the
same BSN module as the DH+ or RIO network.

Figure 3.4 RS-232/485 System

Status LEDs

The table below describes the six LEDs located on the module’s front
panel. To ensure that they are operating correctly, all LEDs are
illuminated during power-up.

Processor

Processor

1747-BSN

1747-BSN

DH485/DF1/ASCII

RS-232/-485 (A) to Link

RS-232/-485 (B) to Link

RS-232/-485 (COM) to Link

RS-232/-485 (A) to CPU

RS-232/-485 (B) to CPU

RS-232/-485 (COM) to CPU

Terminal Block Wiring

LED

Definition

Status & Color

Indication

PRI

Primary

Steady Green

The module is in the primary mode.

SEC

Secondary

Steady Amber

The module is in the secondary mode.

RIO

RIO Communication

Steady Green

The RIO link is working properly.

Flashing Green

A remote device is not configured or connected correctly, or is faulted.

Flashing Red

The RIO link has a fault. The scanner is connected incorrectly, or all devices are
configured improperly, have no power, or are faulted.

Steady Red

There is a configuration error.

Off

The communication channel is not configured as RIO.

ERR

Back-up Module Error

Flashing Red

The module is not ready for switchover.

Off

The module is ready for switchover.

HSSL

High-Speed Serial Link
Communication

Flashing Green

The link is operating with no errors.

Off

A communications error has been detected on the HSSL.

FLT

Fault

Steady Red

A hardware fault has occurred.

Flashing Red

The module is not configured properly.