Network specifications, Throughput introduction – Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 166

Advertising
background image

Publication 1747-UM010B-EN-P - September 2003

A-2 Specifications

Network Specifications

Baud Rate Determination of Maximum Cable Length and
Terminating Resistor Size

DIP Switch Position for Baud Rate Selection

Throughput Introduction

RIO throughput is defined as the time between when an input event
occurs at an I/O module in an RIO chassis to when an output event
occurs at an I/O module within the same RIO chassis. There are three
types of throughput concerning the 1747-BSN Backup Scanner
Module and its RIO network:

discrete throughput (time from discretely mapped input to
discretely mapped output) without block transfers (BTs) present

discrete throughput (time from discretely mapped input to
discretely mapped output) with BTs present

BT throughput (time from when a BT is enabled to when the BT
successfully completes)

Baud Rate

Max. Cable
Distance
(Belden™ 9463)

Resistor Size

Using Extended
Node Capability

57.6K baud

3048 m (10,000 ft.)

82

1/2 Watt

Gray-Red-Black-Gold

115.2K baud

1524 m (5,000 ft.)

230.4K baud

762 m (2,500 ft.)

Not Using
Extended Node
Capability

57.6K baud

3048 m (10,000 ft.)

150

1/2 Watt

Brown-Green-Brown-Gold

115.2K baud

1524 m (5,000 ft.)

230.4K baud

762 m (2,500 ft.)

82

1/2 Watt

Gray-Red-Black-Gold

Position 1

Position 2

Baud Rate

ON

ON

57.6K

ON

OFF

115.2K

OFF

ON

230.4K

OFF

OFF

Disabled

Advertising