Publication 1747-UM010B-EN-P - September 2003

Programming Techniques 9-7

0016

B3:3

15

COP

Copy File
Source #M1:1.5420
Dest

#N19:128

Length

128

COP

B3:4

15

0017

MOV

Move
Source

B3:4

0010000001000000<
Dest

M0:1.3411

?<

MOV

0018

END

This rung copies the "new" Data Block #16 data from the secondary 1747-BSN to a file within the secondary processor. When the Copy is
complete, the DTHW (Data Table Handshake Word) bit for Data Block #16 (B3:4/15 = M0:1.3411/15) must be set to inform the secondary
1747-BSN that the secondary processor has received the latest Data Block and is now ready for the next block of data via Data Block #16.

This rung copies the virtual DTHW word (B3:4) to the actual DTHW word (M0:1/3411) located in the 1747-BSN module. M-file accesses are
interrupts to the processor. Using virtual words minimizes M-file accesses, thereby minimizing the effects of these transfers on the ladder
program scan time.

Virtual DTHW bit for Data Block #16

Virtual and Actual DTHW words