A-10 Specifications

1. Use the throughput formula to calculate the maximum

throughput of the 1747-ASB module.

T

dm-bt

=

2T

ps

+

2T

RIO

+ 2T

btx

+

T

adp

+ T

SNo-bt

+ T

SNi

+ T

id

+ T

od

T

ps

= 25.0 ms, which is from the APS reference manual (assume

for example)

T

RIO

= The total RIO scan time (ms)

T

btx

= Additional time due to sending any BT data on the RIO

link

T

adp

= Two 1747-ASB module backplane scan times (calculated

from ASB manual = 2(4.5) = 9.0 ms

T

SNo-bt

= 22.0 ms from the table on page B-13, TSNo with Block

Transfers (Normal Mode). There are 3 logical racks configured.

T

SNi

= 5.0 ms

T

id

= 10.0 ms, which is from I/O module instruction sheets

T

od

= 1.0 ms, which is from I/O module instruction sheets

T

dm-bt

= 2(25.0) + 2T

RIO

+ 2T

btx

+ 9.0 + 22.0 + 5.0 + 10.0 + 1.0

2. Calculate the total RIO scan time (T

RIO

).

Locate the baud rate

(115.2K) and adapter size which is found in the table on page
B-4. Multiply the RIO scan times listed under the 115.2K
heading by the number of each different type of rack that you
have. Add those number together.

T

RIO

= Tadapter1 + Tadapter2 + Tadapter3

T

RIO

= 1(5.5) + 1(4.0) + 2(3.5)

T

RIO

= 16.5 ms