Publication 1747-UM010B-EN-P - September 2003

1-12 Overview

Guidelines for Configuring Complementary I/O

When you configure your remote system for complementary I/O,
follow these guidelines:

You can place an output module in the primary chassis opposite
another output module in the complementary chassis; they use
the same bits in the output image table. However, we do not
recommend this placement of modules for redundant I/O.

You cannot use complementary I/O with a chassis that uses
32-point I/O modules and 1-slot addressing or 16-point I/O
modules with 2-slot addressing.

Do not place an input module in the primary chassis opposite
an input module in the complementary chassis because they use
the same bits in the input image table.

2-Slot Addressing

The figures below illustrate a possible module placement to configure
complementary I/O using 2-slot addressing.

I
8

O

8

I
16

I
8

I
8

O

8

O

16

O

8

O

BT

BT

8

O

8

O

8

O

8

I

8

I

8

I

8

I

8

O

8

1

0

1

2

3

4

5

I

16

I

16

I

16

O

16

O
16

O
16

0

1

2

3

4

5

I

16

I

16

I

16

O

16

O

16

O
16

1

E

M

P
T

Y

Outputs in the complementary chassis would use the same bits in the

output image table as the outputs in the primary chassis. You cannot

place inputs in the complementary chassis.

E

M

P
T
Y

E

M

P
T
Y

E

M

P
T
Y

E

M

P
T
Y

Primary

I = Input Module (8- or 16-point)
O = Output Module (8- or 16-point)
BT = Block Transfer Module

Primary

Complementary

Complementary

(1) Must be empty if corresponding primary slot is a block transfer module.

IMPORTANT

With 2-slot addressing, if an input module resides in
either slot associated with a logical group of the
primary chassis, an input module cannot reside in
that logical group's complementary chassis.