Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 154

Advertising
background image

Publication 1747-UM010B-EN-P - September 2003

9-12 Programming Techniques

0023

B3:5

11

B3:6

11

COP

Copy File
Source #N17:128
Dest

#M0:1.4908

Length

128

COP

L

B3:7

11

0024

B3:6

11

U

B3:7

11

0025

B3:5

12

B3:6

12

COP

Copy File
Source

#N18:0

Dest #M0:1.5036
Length

128

COP

L

B3:7

12

0026

B3:6

12

U

B3:7

12

0027

B3:5

13

B3:6

13

COP

Copy File
Source #N18:128
Dest

#M0:1.5164

Length

128

COP

L

B3:7

13

0028

B3:6

13

U

B3:7

13

Virtual DTSW Bit

for Data Block #12

Virtual DTHW Bit for

Data Block #12

This rung monitors the DTCW and DTSW bits for Data Block #12. When a transfer of data using Data Block #12 is not in progress, copy
up to 128 words to the appropriate M-file location for Data Block #12 in the 1747-BSN module.

Virtual DTCW Bit for Data Block #12

Unlatch the virtual DTCW bit for Data Block #12 when the comparable virtual DTSW bit is set by the 1747-BSN module to indicate that it has
received the last data via Data Block #12. When B3:7/11 has been unlatched, the module is ready for the next data transfer via Data Block #12.

Virtual DTSW Bit

for Data Block #13

Virtual DTHW Bit for

Data Block #13

This rung monitors the DTCW and DTSW bits for Data Block #13. When a transfer of data using Data Block #13 is not in
progress, copy up to 128 words to the appropriate M-file location for Data Block #13 in the 1747-BSN module.

Virtual DTCW Bit for Data Block #13

Virtual DTHW Bit for Data Block #12

Virtual DTCW Bit for Data Block #12

Virtual DTCW Bit for Data Block #14

Virtual DTHW Bit for Data Block #14

Unlatch the virtual DTCW bit for Data Block #14 when the comparable virtual DTSW bit is set by the 1747-BSN module to indicate that it has
received the last data via Data Block #14. When B3:7/13 has been unlatched, the module is ready for the next data transfer via Data Block #14.

Virtual DTSW Bit

for Data Block #14

Virtual DTHW Bit for

Data Block #14

This rung monitors the DTCW and DTSW bits for Data Block #14. When a transfer of data using Data Block #14 is not in
progress, copy up to 128 words to the appropriate M-file location for Data Block #14 in the 1747-BSN module.

Virtual DTCW Bit for Data Block #14

Virtual DTCW Bit for Data Block #13

Virtual DTHW Bit for Data Block #13

Unlatch the virtual DTCW bit for Data Block #13 when the comparable virtual DTSW bit is set by the 1747-BSN module to indicate that it has
received the last data via Data Block #13. When B3:7/12 has been unlatched, the module is ready for the next data transfer via Data Block #13.