Compatible devices -20, Compatible devices – Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 34

Advertising
background image

Publication 1747-UM010B-EN-P - September 2003

1-20 Overview

Baud Rate Settings

Module Address Switch

The four-position Module Address DIP switch configures the BSN
address in the LSL. The following table shows the address that
corresponds to each setting.

Compatible Devices

The 1747-BSN is compatible with all Remote I/O adapter devices.

Position 1

Position 2

Baud Rate

ON

ON

57.6K

ON

OFF

115.2K

OFF

ON

230.4K

OFF

OFF

Disabled

Switch Position

1747-BSN Address

1

2

3

4

OFF

OFF

OFF

Not U

sed

1

ON

OFF

OFF

2

OFF

ON

OFF

3

ON

ON

OFF

4

OFF

OFF

ON

5

ON

OFF

ON

6

OFF

ON

ON

7

ON

ON

ON

8

IMPORTANT

The module address must equal the actual slot
number or the module will fault. For example, the
1747-BSN module in slot 1 must have an address
equal to 1.