1-20 Overview
Baud Rate Settings
Module Address Switch
The four-position Module Address DIP switch configures the BSN
address in the LSL. The following table shows the address that
corresponds to each setting.
Compatible Devices
The 1747-BSN is compatible with all Remote I/O adapter devices.
Position 1
Position 2
Baud Rate
ON
ON
57.6K
ON
OFF
115.2K
OFF
ON
230.4K
OFF
OFF
Disabled
Switch Position
1747-BSN Address
1
2
3
4
OFF
OFF
OFF
Not U
sed
1
ON
OFF
OFF
2
OFF
ON
OFF
3
ON
ON
OFF
4
OFF
OFF
ON
5
ON
OFF
ON
6
OFF
ON
ON
7
ON
ON
ON
8
IMPORTANT
The module address must equal the actual slot
number or the module will fault. For example, the
1747-BSN module in slot 1 must have an address
equal to 1.