Application Examples 6-9

Ladder File 9 - HSCE2 Initialization Routine

Programming ladder file 9 shows the indirect addressing required to
set up the programming blocks in this example.

0000

LES

Less Than (A<B)
Source A

N11:0

170<
Source B

N11:1

170<

LES

O:1

15

I:1

15

COP

Copy File
Source #N10:[N11:0]
Dest

#O:1.0

Length

8

COP

L

O:1

15

0001

O:1

15

I:1

15

U

O:1

15

MEQ

Masked Equal
Source

I:1.0

265<
Mask

6000h

24576<
Compare

0

0 <

MEQ

ADD

Add
Source A

N11:0

170<
Source B

10

10 <
Dest

N11:0

170<

ADD

0002

EQU

Equal
Source A

N11:0

170<
Source B

N11:1

170<

EQU

O:1

15

I:1

15

COP

Copy File
Source #N10:[N11:0]
Dest

#O:1.0

Length

8

COP

L

B3:0

0

0003

0004

END

DATA_BLOCK_PTR

DATA_BLOCK_PTR

DATA_BLOCK_PTR

#HSCE2_CFG_BLK

#HSCE2_CFG_BLK

HSCE2_INIT_DONE

HSCE2_XMIT

1746-HSCE2

HSCE2_XMIT

1746-HSCE2

HSCE2_XMIT

1746-HSCE2

1746-HSCE2

HSCE2_ACK

HSCE2_XMIT

1746-HSCE2

1746-HSCE2

HSCE2_ACK

HSCE2_XMIT

1746-HSCE2

1746-HSCE2

HSCE2_ACK

L

B3:0

1

I:1

15

I:1

14

I:1

13

HSCE2_ACK

HSCE2_FAULT

1746-HSCE2

1746-HSCE2

1746-HSCE2

HSCE2_PERR

HSCE2_ERROR

If the blocks have not all been transmitted (block data offset < max block offset), copy block to the HSCE2 and set transmit bit (O:e.0/15).

When HSCE2 sets its acknowledge bit (I:e.0/15), reset the module transmit bit (O:e.0/15) and check HSCE2
error bits (I:n.1). If no error bits are ON, increment the block counter to permit the next move to start.

When the last block is completed (block data offset = max block offset), copy the Counter Control Block to the HSCE2.
Note: The Counter Control Block does not require a 0-1 positive transition of the transmit bit to operate.

If the programming error bit or the module fault bit is set, set the HSCE2 error bit.