Module Operation 2-9

Counter Types

Each counter can be programmed to operate as a linear or ring
counter. Both types are described below.

Linear Counter

The figure below demonstrates linear counter operation. In linear
operation, the count value must remain within the programmed
minimum/maximum values. If the count value goes above or below
these values, the counter stops counting, and an overflow/underflow
bit is set. In the overflow or underflow condition, the rate value
continues to be updated and valid.

The number of pulses accumulated in an overflow/underflow state
are ignored. The counter begins counting again when pulses are
applied in the proper direction. For example, if you exceed the
maximum by 1,000 counts, you do not need to apply 1,000 counts in
the opposite direction before the counter begins counting down. The
first pulse in the opposite direction decrements the counter.

Figure 2.5 Linear Counter Diagram

Count Up

Count Down

Counter Value

Maximum Value

Overflow

Minimum Value

Underflow

0