Single-ended encoder wiring (open collector) -9, 9 and 3-10, Single-ended encoder wiring (open collector) – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual

Page 49: Single-ended encoder output waveforms

Advertising
background image

Publication 1746-UM002B-EN-P - August 2004

Installation and Wiring 3-9

Single-Ended Encoder Wiring (Open Collector)

Figure 3.7 Single-Ended Encoder Wiring

(1) Refer to your encoder manual for proper cable type. The type of cable used should be twisted-pair, individually

shielded cable with a maximum length of 300m (1000 ft.).

(2) Calculate the value of the pull-up resistor (R), as shown below:

For 5V dc jumper position:

For 24V dc jumper position:

where:R = pull-up resistor value

Vcc = power supply voltage
Vmin = 4.2 V dc
Imin = 6.3 mA

Single-Ended Encoder Output Waveforms

The figure below shows the single-ended encoder output waveforms.
When the waveform is low, the encoder output transistor is on. When
the waveform is high, the encoder output transistor is off.

Figure 3.8 Single-Ended Encoder Output Waveforms

Power Supply Voltage (Vcc)

Pull-up Resistor Value (R)

5V dc

127

12V dc

238

24V dc

2140

A

B

Z

A1(+)

A1(–)

B1(+)

B1(–)

Z1(+)

Z1(–)

GND

VS

+VDC

COM

R

(2)

Cable

(1)

Power
Supply

Allen-Bradley
845H Series
single-ended
encoder

shield/housing
Connect only if housing is electronically
isolated from the motor and ground.

Shield

Module Inputs

Earth

R

Vcc

Vmin

(

)

Imin

--------------------------------------

=

R

Vcc

Vmin

(

)

Imin

--------------------------------------

1K

=

A

B

Z

Advertising