1-4 Module Overview

Operating Class

Module operation differs slightly based on the operating class. The
operating class is selected via the module ID code.

Class 1

Class 1 operation is compatible with all SLC 500 processors. In Class 1
operation, the module uses 8 input and 8 output words and has an
associated ID code of 3511. A maximum of four 16-bit counters are
available in this operating class.

Class 4

Class 4 operation is compatible with SLC 5/03 and above systems. In
Class 4 operation, the module uses 23 input and 8 output words and
has an associated ID code of 15912. A maximum of four 24-bit
counters are available in this class.

Class 1 vs. Class 4 Comparison

Class

Class 1

Class 4

Counters

16-bit (±32,767)

24-bit (±8,388,607)

Input Words

8 with limited information.

23 with all information.

Backplane Interrupts

Not permitted.

Permitted.

Use in RIO Chassis

Permitted.

Not permitted.

Use in ControlNet Chassis

Not permitted.

Permitted.

Module ID Code

3511

15912