Ladder file 9 - hsce2 initialization routine -17, Ladder file 9 - hsce2 initialization routine, See the ladder logic from example 2 on page 6-9 – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual

Page 109

Advertising
background image

Publication 1746-UM002B-EN-P - August 2004

Application Examples 6-17

Ladder File 8 Continued

Ladder File 9 - HSCE2 Initialization Routine

See the ladder logic from Example 2 on page 6-9.

0003

B3:0

6

SOFT_PRESET_OSR

O:1

17

1746-HSCE2

HSCE2_CFG_BLK/17

CPT

Compute
Dest

F8:0

130.0<

Expression ( 1000.0 * I:1.2 ) + I:1.3

CTR1_COUNTS

CPT

Compute
Dest

F8:1

140.0<

Expression ( ( N10:25 * 1000.0 ) + N10:26 ) + 10.0

PRESET_UPPER_LIMIT

CPT

Compute
Dest

F8:2

120.0<

Expression ( ( N10:25 * 1000.0 ) + N10:26 ) - 10.0

CPT

PRESET_LOWER_LIMIT

LIM

Limit Test
Low Lim

F8:2

120.0<

Test

F8:0

130.0<

High Lim

F8:1

140.0<

LIM

CTR1_COUNTS

U

O:1

17

1746-HSCE2

HSCE2_CFG_BLK/17

0004

END

0002

B3:0

0

HSCE2_INIT_DONE

B3:0

6

SOFT_PRESET_TRGR

OSR

B3:0

7

SOFT_PRESET_OSR

L

O:1

17

1746-HSCE2

HSCE2_CFG_BLK/17

This rung implements a soft preset of counter 1 when the soft preset trigger bit sees a positive change (0 to 1). The rung assumes that the
Counter Control Block (last configuration block) is still in the output image to the 1746-HSCE2, and that Counter 1 permits soft presets.

After the soft preset is complete, unlatch the soft preset bit (O:1.1/1). To determine if the soft
preset is complete, compute the current counter 1 count value (F8:0), compute the valid preset
range (this example uses ±10 + PRESET VALUE from the Min/Max Count block), and compare.