Throughput and timing, On-state current derating – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual

Page 121

Advertising
background image

Publication 1746-UM002B-EN-P - August 2004

Specifications A-3

On-State Current Derating

Throughput and Timing

2.0 A

1.5 A

1.0 A

0.5 A

20˚C

0˚C

40˚C

60˚C

Temperature

Ma

ximu

m On

-St

ate

Cur

re

nt

(p

er

m

od

ul

e)

Operation

Description

Timing (µs)

Minimum

Typical

Maximum

Throughput

The delay between the time the module receives a pulse and when
its real outputs and the SLC backplane are updated (based on a
count range).

300

700

1600

Input File Update
Time

The delay between the time the module receives a pulse and when
the backplane count value is updated, including setting the I/O
interrupt.

300

600

1500

Output Turn-on
Time

The time it takes for the real output to reach 90% output voltage
after commanded by the module, not including SLC scan time.

10

Output Turn-off
Time

The time it takes for the real output to reach 10% output voltage
after commanded by the module, not including SLC scan time.

100

Inductive Turn-off
Time

The time between the module receiving an input pulse and breaking
contact in a BULLETIN 110 contactor.

50

Rate Accuracy

The accuracy of the reported rate as compared to actual input rate in
the equation: reported rate/actual input rate.

0.005%

0.015%