Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual

Page 39

Advertising
background image

Publication 1746-UM002B-EN-P - August 2004

Module Operation 2-19

C/R: Count/Rate Bit

The count/rate bit is used only in Class 1 operating mode. Because
only one data word is available for Counters 2 and 3 in operating
mode 2, and one data word for each of the four counters in operating
mode 3, the module transfers either the counter’s count or rate value.

When this bit is reset (0), the data in the corresponding word is the
count value. When this bit is set (1), the data in the corresponding
word is the rate value.

ROvF: Rate Overflow Bit

This bit is set when the rate is greater than the maximum rate value.

RUdF: Rate Underflow Bit

This bit is set when the rate is less than the minimum rate value.

COvF: Counter Overflow Bit

When the counter is configured as a linear counter, this bit is set when
the count would become one over the maximum count value.

CUdF: Counter Underflow Bit

When the counter is configured as a linear counter, this bit is set when
the count would become one under the minimum count value.

CState: Counter State Bits

These two bits show the operational state of the counter.

Table 2.3 Counter State Bit Settings

TIP

Counter overflow or underflow bits are reset when a
pulse in the opposite direction is received.

Bits 09 or 01

Bits 08 or 00

Operating State

0

0

Stopped

0

1

Running

1

0

Hold

1

1

Reserved