Configuration and Programming 4-17

Figure 4.7 Min./Max. Rate Value Block

Programming Block Identification Bit

(Word 0, Bit 03)

This bit identifies the type of block.

TRMT: Transmit Bit

(Word 0, Bit 15)

A 0 to 1 transition starts a programming cycle.

DEBUG: Debug Mode Selection Bit

(Word 0, bit 12)

When this bit is set, the debug mode is activated. Debug mode returns
the input data file showing current settings in the Min./Max. Rate
Value block. For details, see Debug Mode Operation on page 5-7.

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Word 0

TRMT

0

0

DEBUG

0

CNTR

No.

0

0

0

0

1

0

0

0

Word 1

Minimum Rate Value in integer or floating point notation

Word 2

Word 3

Maximum Rate Value in integer or floating point notation

Word 4

Word 5-7

RESERVED: Must equal zero