Publication 1746-UM002B-EN-P - August 2004

2-8 Module Operation

Gate and Preset Limitations

Because only the Z inputs are used for external gating and presetting,
the only gate/preset modes available for Counters 3 and 4 are No
Preset and Soft Preset Only. All six modes are always available for
Counters 1 and 2.

Gate and Preset Considerations

Z-pulse Preset Operation

In applications where the Z pulse of the encoder is being used to
preset the position, and where the Z pulse of the encoder is aligned
with either the A or B pulses, the capture or count value may be
affected by ± 1 count. If the Z pulse is edge aligned with the A pulse,
preset operations may not be performed accurately in any of the
quadrature modes. If the Z pulse is edge aligned with the B pulse,
preset operation may not be performed accurately in the X4
quadrature mode only. A small capacitor (for example, 0.01 µF) across
the Z inputs will dis-align these inputs and should correct this
condition.

Summary of Available
Counter Configurations

The table below summarizes the input configurations and gate/preset
modes available for all counters, based on operating mode.

IMPORTANT

In Class 1, Operating Mode 2, Counter 2 does not
have a capture value available. In Class 1, Operating
Mode 3, no capture values are available.

Operating
Mode

Counter

Input Configuration

Gate/Preset Mode

1

1

All

All

2

All

All

2

1

All

All

2

Pulse/Internal Direction

All

3

Pulse/Internal Direction

No Preset or Soft Preset Only

3

1

Pulse/Internal Direction

All

2

Pulse/Internal Direction

All

3

Pulse/Internal Direction

No Preset or Soft Preset Only

4

Pulse/Internal Direction

No Preset or Soft Preset Only