Programming block identification bit, Trmt: transmit bit, Debug: debug mode selection bit – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual

Page 70

Advertising
background image

Publication 1746-UM002B-EN-P - August 2004

4-20 Configuration and Programming

Figure 4.8 Program Ranges Block

Programming Block Identification Bit

(Word 0, Bit 04)

This bit identifies the type of block.

TRMT: Transmit Bit

(Word 0, Bit 15)

A 0 to 1 transition starts a programming cycle.

DEBUG: Debug Mode Selection Bit

(Word 0, bit 12)

When this bit is set, the debug mode is activated. Debug mode returns
the input data file showing current settings in the Program Ranges
block. For details, see Debug Mode Operation on page 5-7.

15 14 13 12 11 10 09 08 07 06

05

04 03 02 01 00

Word 0

TRMT

0

0

DEBUG

0

RT

ype

CNTR

No

0

0

0

1

0

0

0

0

Word 1

Range Number

Word 2

Range Start Value

Word 3

Word 4

Range Stop Value

Word 5

Word 6

0

0

0

0

0

0

0

0

Output State

Virtual

Real

Word 7

RESERVED: Must equal zero

Advertising