CHAPTER 5 - SETUP

5-7

the number of decimal places in the 32
bit integer weight outputs. The value 0
causes these weight outputs to be in
floating point format.

NOTE:

This applies ONLY to the weights as viewed through
the I/O (Command) interface. The explicit message
interface continues to use 3 decimal place 32 bit inte-
ger format only.

Parameter 38 = Write non-volatile com-
mand.
Length in Bytes = 1

Setting this parameter to 1 will cause a
save to non-volatile memory. Calibra-
tion data is saved to non-volatile memory
automatically. Other parameters must be
saved using this command.

Parameter 39 = Parameter high word.
Length in Bytes = 2
This parameter is used in the command
interface as described below:

Command
Interface

The Command Interface allows easy access
to all parameters without using explicit mes-
sages.
The HI 200DNWM version 2.1 produces 4
bytes of polled output data and consumes 4
bytes of polled input data. The 4 bytes of
input data can be used to set parameters in
the module and to specify what data should
be placed in the 4 bytes of output data.