CHAPTER 6 - CALIBRATION

6-3

36. The DeviceNet Weigh
Module Dialog Box appears.

Step 4. Click on the Parameter tab. The

Parameter List appears with the
information for the weigh mod-
ule at address 36.

Step 5. Click on Cal LO.
Step 6. Enter the Cal LO value.
Step 7. Click on the Apply button.
Step 8. Click on Yes.
Step 9. Click on C2 Cal Cmd.
Step 10. Set the C2 Cal Cmd to “1”.
Step 11. Click on the Apply button.
Step 12. Click on Yes.
Step 13. Click on Cmd Save non-vol.
Step 14. Set the Cmd Save non-vol to

“1”.

Step 15. Click on the Apply button.
Step 16. Click on Yes.
Step 17. The calibration is complete.

NOTE:

Requires C2

®

load sensors or load points.

NOTE:

RS NetWorx® is a registered trademark of Rock-
well Automation.

Test Weight Calibra-
tion from RS Net-
Worx

®

Step 1. On the PC open RS NetWorx

®

Step 2. Browse the Network.
Step 3. Double click on the Node Icon

of the weigh module you want
to calibrate. For example: Node
36. The DeviceNet Weigh
Module Dialog Box appears.

Step 4. Click on the Parameter tab. The

Parameter List appears with the
information for the weigh mod-
ule at address 36.

Step 5. Click on Span Weight.