Comtrol ES8510-XT User Manual

Page 197

Advertising
background image

RocketLinx ES8510 and ES8510-XT User Guide: 2000513 Rev. H

Modbus TCP Register Table - 197

ModBus TCP /IP Support

0x020A

2 words

Firmware Release Date

Firmware was released on 2010-08-11 at 09
o’clock

Word 0 = 0x0B09

Word 1 = 0x0A08

0x020C

3 words

Ethernet MAC Address

For example: MAC = 01-02-03-04-05-06

Word 0 Hi byte = 0x01

Word 0 Lo byte = 0x02

Word 1 Hi byte = 0x03

Word 1 Lo byte = 0x04

Word 2 Hi byte = 0x05

Word 2 Lo byte = 0x06

0x0300

2 words

IP address

For example: IP = 192.168.250.250

Word 0 Hi byte = 0xC0

Word 0 Lo byte = 0xA8

Word 1 Hi byte = 0x0A Word 1 Lo byte = 0x01

0x020F to 0x2FF

241 words

Reserved address space

0x0302

2 words

Subnet Mask

0x0304

2 words

Default Gateway

0x0306

2 words

DNS Server

0x0308 to 0x3FF

248 words

Reserved address space (IPv6 or others)

0x0400

1 word

AC1

0x0000:Off

0x0001:On

0xFFFF: unavailable

0x0401

1 word

AC2

0x0000:Off

0x0001:On

0xFFFF: unavailable

0x0402

1 word

DC1

0x0000:Off

0x0001:On

0xFFFF: unavailable

0x0403

1 word

DC2

0x0000:Off

0x0001:On

0xFFFF: unavailable

0x0404 to 0x040F

12 words

Reserved address space

Word Address

Data Type

Description

Advertising