Connecting to a DC Power Source (C364T NEBS Only)

Issue 1 July 2006

51

Connecting to a DC Power Source (C364T NEBS Only)

The C364T NEBS is rated -36 to -60 VDC, 2A.

!

CAUTION:

CAUTION:

A UL-Listed and CSA-Certified branch circuit protective device of up to 20A must
be provided in the building DC mains wiring installation for branch circuit
protection.

!

CAUTION:

CAUTION:

Always connect the ground wire first and disconnect it last.

Figure 17: Avaya C360 DC Input Terminal Block

The terminals are marked with

, “+” and “-“.

The size of the two screws in the terminal block is M4.

The pitch between each screw is 9.5mm.

4. Remove the protective plastic cover over the DC inputs by unscrewing the two Phillips

screws.

!

WARNING:

WARNING:

The conductors to be used for connecting the DC power supply to the C360 must
be UL Recognized and CSA Certified and be a minimum of 16 AWG or have a
cross-sectional area of 1.0mm

2

.

!

ADVERTENCIA:

ADVERTENCIA:

Los conductores que se utilizarán para conectar la fuente de alimentación
externa con el C360 deben ser Reconocidos por UL, Certificados por CSA y ser
como mínimo de 16 AWG o tener un área de sección transversal de 1.0 mm

2

.

5. Connect the power cable to the terminals on the C360 and to the external DC power supply

in the following sequence:

1. Ground wire to grounding post

Figure notes:

1. Protective plastic cover

2. BUPS DC input terminals

3. Grounding post

1

2

3