To add and configure a DACT module:
1. Select the Dialer function from the system panel.

2. Click the Add Device button. The “Add Dialer” window displays.

Figure 143. Example of Add Dialer Window


3. In the “Phone Line 1 and Phone Line 2” fields, make any necessary changes.

Figure 144. Example of Phone Lines Options

y

Enter the number of rings you want the DACT to pickup when receiving a call.
Note: If you do not change the default from "0", the DACT will never pick up a call!

y

Enter the appropriate line prefix, if any is required for your phone lines.
Example: In the example shown above, the phone line requires that "9" is dialed to get an outside line.

The two ",," (commas) instruct the dialer to pause 2 seconds before dialing the reporting account numbers.

4. In the “Reporting Accounts” section, make the necessary selections for the primary and secondary reporting accounts:

y

Select the Report type(s): Alarms, Troubles, Supervisory

y

Enter the Accounts IDs and Phone Numbers

y

Select the Primary Report By option: Panel, Zone orPoint

y

Choose the Primary Format option: CID / SIA

Note: Both SIA-DCS and Ademco Contact ID protocols are supported.

Figure 145. Example of Report Accounts Setup

The "Primary" account setting

fields are displayed here.

Each "," (comma) creates

a 1-second pause before

the dialer attempts to dial a

reporting account number.