Slc current draw worksheet – Potter PFC-6075R User Manual

Page 17

Advertising
background image

2-11

PFC-6075R • 5403594 • REV D • 9/14

SLC Current Draw Worksheet

Device Type

Qty

Standby

(mA)

Total

Standby

(mA)

Alarm

(mA)

Total

Alarm

(mA)

Analog photo smoke detector (PSA)

0.325

0.325

Analog photo DUCT smoke detector (DSA)

0.325

0.325

Analog photo smoke / fixed heat detector (PSHA)

0.325

0.325

Analog fixed heat detector (FHA)

0.325

0.325

Analog combo heat detector (RHA)

0.325

0.325

Conventional initiating zone module - 4 inch mount (CIZM-4) *Note 1

0.325

1.000

Miniature contact module (MCM)

0.325

0.325

Single contact module - 4 inch mount (SCM-4)

0.325

1.000

Dual contact module - 4 inch mount (DCM-4)

0.325

1.000

Monitored output module - 4 inch mount (MOM-4) *Note 2

0.325

1.000

Twin relay module - 4 inch mount (TRM-4)

0.325

1.000

Short circuit isolator (SCI)

0.325

2.34

Analog sounder base (ASB) *Note 3

0.325

0.325

Analog relay base (ARB) *Note 4

0.325

0.325

Isolator base (AIB)

0.325

2.34

SLC alarm LED Current

n/a

n/a

n/a

27.0

SLC Standby

Current

SLC Alarm

Current

* Note 1: CIZM requires 24VDC power source. Standby current Style D = 4.90 mA, Style B (8.5 mA). Alarm Current = 50.0 mA

* Note 2: MOM requires 24VDC power source. Standby current = 1.60 mA. Alarm Current = 1.60 mA

* Note 3: ASB requires 24VDC power source. Standby current = 5 mA. Alarm Current = 100 mA

* Note 4: ARB requires 24VDC power source. Standby current = 5 mA. Alarm Current = 50 mA

Advertising