Input circuits – Potter PFC-6075R User Manual

Page 116

Advertising
background image

6-110

PFC-6075R • 5403594 • REV D • 9/14

Input Circuits

The panel is equipped with two (2) input circuits, I1 and I2, that are low voltage, power limited, and supervised. When

configured, the circuits function as dry-contact monitoring circuits.

Note: These circuits operate as Class B only. Please refer to the figure shown below.

Configuration Characteristics

• Maximum allowable wire length is 10,000 feet.

• Maximum allowable wiring resistance is 100 ohms.

• Maximum wiring capacitance is 1 uF.

• Maximum IDC voltage is 24 VDC, and current is 15 ma.

Figure 152. Example of PSN-1000 / PSN-1000(E) Input Circuit – Normal Open Dry Contact

Notes:

1. The Potter part number for the listed end of line assembly is #3005013 EOL Resistor Assembly.

2. The panel has ground fault detection on the input circuits. The impedance to ground for ground fault detection is 0 ohms.

3. The end of line resistor is a 5.1K ohm resistor.

Wiring to Control Panel

The control panel communicates with and supervises the PSN-1000/PSN-1000(E) via the main P-Link circuit. This connection

is electrically isolated from the rest of the PSN-1000/PSN-1000(E).

Figure 153. P-Link Wiring from Control Panel

-

I1 + - NAC 1 + - NAC 5 + - NAC 3 +

-

+ A B

-

I2 + - NAC 2 + - NAC 4 + - NAC 6 +

-

+ A B

P-LINK

5.1k EOL

Potter Part #3005013

Normally Open

Dry Contact

DWG #602-26

-

+ A B

P-LINK

P-Link from

Control Panel

DWG #602-27