Zone 1: releasing – Potter PFC-6075R User Manual

Page 98

Advertising
background image

5-92

PFC-6075R • 5403594 • REV D • 9/14

Single Interlock (One Count) Releasing Application
This releasing application requires the activation of one zone or a manual release input within a designated releasing zone to

start the release sequence.

Figure 126. Example of Single Interlock (One Count) Releasing Application

One (1) releasing zone contains two (2) input devices and one (1) output. The output configured as releasing is activated when either the

manual station or a detector in the releasing zone are active.

Zone 1: Releasing

1

2

Release

Solenoid

Smoke

Detector

Manual

Release

Cross Zone / Two Count (Double Interlock) Releasing Application
This releasing application requires the activation of two zones or a manual release input within a designated releasing zone to

start the release sequence.

Figure 127. Example 1 of Cross Zone / Two Count (Double Interlock) Releasing Application

One (1) releasing zone contains input and output (device or manual release) with an abort switch. In this application, both sensors in the

releasing zone or a manual release within the designated release zone must be activated to start the release sequence.

Zone 1: Releasing

1

2

NAC Release

Solenoid

Smoke

Detector

Heat Combo

3

Manual

Release

1 & 2 to activate solenoid

OR

3 to activate solenoid

Figure 128. Example 2 of Cross Zone / Two Count (Double Interlock) Releasing Application

Three (3) separate zones are created, each containing one point. In this application, one (1) sensor within each of the cross zones or a manual

release within the designated release zone must be activated to start the release sequence.

Zone 1: Alarm

1

Addr Heat

Combo Detector

Zone 2: Alarm

2

Addr Photo

Heat Detector

NAC Release

Solenoid

Zone 3: Releasing