I/o 1 i/o 2 – Potter PFC-6075R User Manual

Page 34

Advertising
background image

3-28

PFC-6075R • 5403594 • REV D • 9/14

Reverse Polarity Communication Line Circuit

Only I/O 1 and I/O 2 on the PFC-6075R can be programmed as reverse polarity circuits. The short circuit current is rated at

24 VDC and 14 mA maximum. Please refer to the figure below for an example of wiring a reverse polarity communication line

circuit.

Figure 28. Reverse Polarity Communication Line Circuit Wiring

Notes:

1. The panel has ground fault detection on reverse polarity circuits; impedance to ground for ground fault detection

is 0 ohms.

2. The short circuit current is power limited and supervised by a Keltron TTM-RPS transmitter module.

3. When configured for reverse polarity, the PFC-6075R will indicate alarm and trouble events to a remote site.

4. The Alarms override trouble conditions.

DWG #602-8A

Panel

Connection

I/O 1 I/O 2

-

+ -

+

Keltron

TTM-RPS

+

-

Note: IO circuit must configured as a Reverse Polarity circuit.

This connection is limited to same room installation . This connection shall be

limited to 20 feet and enclosed in conduit or equivalently protected against

mechanical injury .