I/o 1 i/o 2, Municipal box connection, Relay output wiring – Potter PFC-6075R User Manual

Page 35

Advertising
background image

3-29

PFC-6075R • 5403594 • REV D • 9/14

Municipal Box Connection

When programmed as a municipal box connection, the circuit power is limited, supervised for open and short circuit conditions,

and provides a local energy connection.

Figure 29. Municipal Box Wiring Example

Notes:

I/O circuits and/or NAC Circuits can be used as Municipal

Box connection .

The EOL device shall be installed in the same electrical enclosure as the Municipal Box.

Panel

Connection

I/O 1 I/O 2

-

+ -

+

Municipal

Box

+

-

End of line device

5.1k ohm 1/2W

Part #3005012

Notes:

1. The trip current for NAC1 and NAC2 is three (3) Amps, and one (1) Amp for I/O1 and I/O2.

2. The maximum voltage rating is 24 VDC.

3. The panel has ground fault detection on municipal box connection circuits. The impedance to ground for ground fault

detection is 0 ohms.

Relay Output Wiring

The panel has three (3) dedicated common relays. The dedicated trouble relay is a fail safe trouble relay that changes position

anytime a trouble condition occurs.

Relays have a contact rating of 24VDC / 3.0A, 125VAC / 3A, and Power Factor of 1.0. These outputs are non-power limited and

not supervised.

Note: If the power supply connected to the devices is power-limited, then the outputs are power limited.

Figure 30. Relay Outputs

TROUBLE

NC COM NO

SUPERVISORY

NC COM NO

ALARM

NC COM NO

DWG #602-9A

DWG #593-26