Fiber interface bridge installation (fib-1000) – Potter PFC-6075R User Manual

Page 44

Advertising
background image

3-38

PFC-6075R • 5403594 • REV D • 9/14

Setting Addresses
The FCB-1000's address is set by dip switch S1. The address must be set in the range of one (1) to thirty-one (1–31) to be

recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.)

Figure 48. FCB-1000 Back Panel View Showing Dip Switch Location

Fiber Interface Bridge Installation (FIB-1000)

The panel supports up to thirty (30) FIB-1000s (Fiber Interface Bridge), which enables the 4-wire P-Link bus to be converted to

and/or from the fiber optic cable.

• Utilizes multimode 62.5/125 micron fiber optic cable

• Cable Length up to 2000 meters or 6500 feet

• Installed in pairs (refer to the "FIB-1000 Wiring" heading for details)

The first installed FIB-1000 can be mounted into any of the compatible fire enclosures, in either of the AE-8 or AE-14, or the

optional rack-mount kit (FIB-1000RM). The FIB-1000RM includes a standard 19 inch rack-mount enclosure, which can then be

installed directly in an equipment rack. The second installed FIB-1000 must be installed in a PSN-1000E cabinet as illustrated in

the following drawings.

Figure 49. FIB-1000 Bridge & FIB-1000RM Rack Mount

DWG #608-11

DWG #608-12

Dip Switch

DWG #608-20

P-Link

Connections

S1