3-40

PFC-6075R • 5403594 • REV D • 9/14

Setting Addresses
The FIB-1000's address is set by dip switch S1, which is located on the back of the board. The address must be set in the range

of one to thirty (1–30) to be recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP

switch programming.)

Figure 52. FIB-1000 Back Panel Showing Dip Switch Location

Serial Parallel Gateway Installation (SPG-1000)

An optional SPG-1000 serial/parallel gateway (printer drive) board can be mounted inside the AE-8 or AE-14 accessory

enclosure, or the AE-RM rack mount enclosure kit. The SPG-1000RM includes a standard 19 inch rack-mount enclosure, which

can then be installed directly in an equipment rack. Up to thirty-one (31) printers may be installed on this panel.

Figure 53. SPG-1000 Serial Parallel Gateway Board & Rack Mount

Figure 54. SPG-1000 Wiring to Control Panel Example

DWG #608-16

DWG #608-15

DWG #608-24

Dip Switches

P-Link

Connections

S1

DWG #608-26

P-Link

-

+ A B

P-Link from

control panel

Example:

Powered by

control panel