Cross Zone Configurations

The purpose of creating cross zones is to ensure that two (2) or more separate zones are activated before an output zone is

triggered.
Although crossing two (2) zones is the most common configuration, up to eight (8) zones may be combined. In this case, when all

the zones that have been crossed are active, the specified outputs will be activated. Several examples of releasing cross zones are

provided in the next topic, “Releasing Zone Configurations”.
To create a cross zone:

1. Create two or more (“Alarm” or “Supervisory” type) zone(s) and name appropriately.
2. Configure and name devices.
3. Move devices into zones.
4. Open the Cross Zones window. Click in the “Enabled” box.

Figure 124. Cross Zones Window Showing Enabled

Note: If the “Enabled” option is not selected, the cross zone relationship will not be in effect.

5. Click on the drop down arrow in the “Input Zone 1” field. All available zones display.

6. Click to select input zone.

7. Repeat steps for the next field, “Input Zone 2” field.

8. Click on drop down arrow in the “Output Zone” field. Select output zone.